296. For stability and economic reasons we operate the transmission line with power angle in the range.
298. For a two-bus system if the change in load at bus 2 is 5 MW and the corresponding change in generation at bus 4 is MW, the penalty factor of bus 4 is
300. A generator is connected to asynchronous motor. From stability point of view it is preferable to have
301. In a 400 kV network, 350 kV is recorded at a 400 kV bus. The reactive power absorbed by a shunt rated for 50 MVAR, 400 kV connected at the bus is
Page 43 of 54